Current article

Calculation of Constant Pressure Values for Relief Valves in the Fire Suppression Systems of High-Rise Buildings


ZHAO Ying 1,WANG Chun-yan2,TAN Wan-fang3

DOI:10.11835/j.issn.1674-4764.2008.03.019

Received ,Revised , Accepted , Available online July 01, 2015

Volume ,2008,Pages -

  • Abstract
The calculation of constant pressure values for relief valves in the fire suppression systems of high-rise buildings usually is based on the working pressure of pipe systems by experience.However,this method only is applied in the condition that the relief valves are installed on the effluent pipes of pumps.In order to confirm the proper constant pressure values of relief valves in fire suppression systems,a formula is deduced using hydraulics theory.The applications of the formula in fire suppression systems are also discussed.The constant pressure values for relief valves are directly related to three factors,namely,the flux and pressure of the fire pump,the located height of the relief valves,and the head loss of flux from the pump exit to the inlets of the relief valves.It is necessary to analyze the working condition of fire suppression systems and to be certain of the permissive pressure range for overpressure.