Current article

Analysis of Sewage-water Heat Exchanger withthe Function of Auto-de-fouling


SHEN Chao,JIANG Yi-qiang and YAO Yang

DOI:10.11835/j.issn.1674-4764.2011.03.019

Received December 26, 2010,Revised , Accepted , Available online July 01, 2015

Volume ,2011,Pages 107-111

  • Abstract
A sewage-water shell-tube heat exchanger with the function of de-fouling was proposed and designed for sewage-source heat pump. Its new simulation program which relies on a distribution parameter computational method was set up. Then the model was solved with the method of Matrix Control. Based on the model, the distribution of bilateral fluid temperature were studied, under the conditions of different flow rates and heat exchange area before and after the de-fouling. Results showed that there will be heat anti-transfer phenomenon if the heat exchanger area is bigger than need and the region of this phenomenon was point out. Setting the function of auto-de-fouling in shell-tube heat exchanger and reducing the equipment's volume accordingly can make the sewage-water heat exchanger run in the best conditions.